Tuesday, July 24, 2012

1207.5100 (Zhao Li et al.)

The Cryogenic System for the Panda-X Dark Matter Search Experiment    [PDF]

Zhao Li, Karl Ludwig Giboni, Haowei Gong, Xiangdong Ji, Andy Tan
Panda-X is a liquid xenon dual-phase detector for the Dark Matter Search. The first modestly-sized module will soon be installed in the China JinPing Deep Underground Laboratory in Sichuan province, P.R. China. The cryogenics system is designed to handle much larger detectors, even the final version in the ton scale. Special attention has been paid to the reliability, serviceability, and adaptability to the requirements of a growing experiment. The system is cooled by a single Iwatani PC150 Pulse Tube Refrigerator. After subtracting all thermal losses, the remaining cooling power is still 82W. The fill speed was 9 SLPM, but could be boosted by LN2 assisted cooling to 40 SLPM. For the continuous recirculation and purification through a hot getter, a heat exchanger was employed to reduce the required cooling power. The recirculation speed is limited to 35 SLPM by the gas pump. At this speed, recirculation only adds 18.5 W to the heat load of the system, corresponding to a 95.2 % efficiency of the heat exchanger.
View original: http://arxiv.org/abs/1207.5100